5. ION Meter Communications Setup
By establishing a Modem connection to the ION meter, we are making a serial
connection between the ION-E Server and the remote station. The physical layer of
the communication is similar to having an RS-232 serial cable linking the Server and
the ION meter. For this reason, minimal configuration is required for the ION 7650
with regards to the wireless modem connection.
1) Ensure that the Serial Port connected to the wireless modem is configured for the
same Baud Rate that you set for the modem (e.g., 9600bps).
2) Ensure that the Protocol on the 7650 meter COM port is set to ION. For
PowerLogic PM meters, it should be set to Modbus RTU.
If you are connecting the ION 7650 to the modem using an RS-232 cable, ensure
that the Comm Port of the 7650 (e.g., COM1) is correctly set for RS-232 mode.
7650 Serial Port Rx Timeout Setting
If you are using Acknowledgement (AckNaks) to detect errors in the communication
link between the ION7650 meter and the ION-E server, you may need to adjust the
Receive Timeout on the COM port of the ION7650 meter. This makes the link more
tolerant of long delays (e.g., ION-E is slow in responding to the meter).
We received reports that values such as 15 seconds were used in Hong Kong and
Australia for ION7650 meters.