Cellular Phone Compatibility Modem AT Commands
Page 10 © 2007 Schneider Electric. All rights reserved.
Cellular Phone Compatibility
Usinganalogcellularphonestocommunicatewithameterequippedwitha
modemisnotrecommendedduetotheinherentunreliabilityofcellularphone
communication.However,ifcellularphone‐to‐metercommunicationis
necessary,werecommendthefollowingsetup:
For compatibility with the (newer) Multi-Tech internal modem:
Localmode m:Mu lti ‐Tech5600ZDXorGVC56K(alsopossiblewithother
Conexantchipsetbasedmodems)
NecessaryATcommands:+MS=11,1,1200,4800\N2
Description:Thissetupforcesv.34atmaximum4800baudandforceserror
correct io n. ThisalsoensuresotherATcommandsdonotturnofferror
correctio nandcompression.The4800settingmay beincreasedto7200/ 960 0,
butinmostcases,using4800resultsinbetterthroughputduetolesserrorsfor
themode mstodealwith.
Fortheaboveapplication,thefollowingarerecommendedmodeminitialization
stringchangesfortheMulti‐Techmodem(insidetheIONmeter):
ATcommand:S10=100
Description:Increasesdisconnecttimeonlossofcarrier
ATcommand:B1
Description:Ifratedropsto1200,useBellprotocol
For compatibility with the (older) Conexant internal modem:
Localmode m:BlackBoxMiniModem56kData/Faxmodem,modelMD1620 A,
orMulti‐TechMultiModem,modelMT5600ZDX
NecessaryATcommands:%E0‐K1‐SEC=1+MS=10,1,1200,9 600
Description:Thissetupallowsthemodemtonegotiate anybaudratebetween
1200and9600bps.Thissetupalsopreventsv.34connectionsbynotallowing
themode m tonegotiateanythinghigherthanV32bis.
Fortheaboveapplication,thefollowingarerecommendedmodeminitialization
stringchangesfortheConexantmodem(insidethe
IONmeter):
ATcommand:AT%E0‐K1‐SEC=1+MS=10,1,1200,9600
Inaddition,themodemsiteneedstobesetupasfollows,regardlessoftheactual
connectionbaudrate:
ModemType:BlackBoxMiniModem56kData/F ax
TransmitDelay:10ms
BaudRate:9600bps
RTS/CTS:unchecked
ReceiveTimeout:5000ms
ByteTimeout: 20byte‐time