Modem AT Commands Changing the Internal Modem Settings
© 2007 Schneider Electric. All rights reserved. Page 9
Changing the Internal Modem Settings
ToreconfiguretheIONmeter’sinternalmodem,accessitssetupregister:
UsingIONEnterprise®:
InDesigner,rightclicktheinternalmod em’sCommmodule(insidethe
CommunicationsSetupgroup).
UsingIONSetup:
DoubleclicktheCommmoduleiconforthemetersinternalmo dem.Ifyou
cannotseethemodule,rightclickthemetericon.IntheDevicePropertiesdialog
box,click theToolstab,thenselect “ShowAdvancedIONSetup”intheDevice
Setupbox.ClickOK.
Changing the Local Modem Settings
Using PEGASYS or ION Setup software:
PEGASYSandIONSetupusethemodem.inifiletodefinehowthelocalmodem
shouldbehavewhenevermodemcommunicationisinitiated.Themodem.inifile
containsinformationthatsetsthelocalmodemtothespecifiedbaudrateandturns
compressionanderrorcorrection off.Thisparticularsettingisusefulonlyif
there
are3700SeriesmetersconnectedtotheIONmeter’sinternalmodem
communicationsloop(throughModemGate).IfonlyIONmetersareused,we
recommendthatonlytheminimumrequiredmodem.inisettingsbeused(i.e.Q0
E0V1&K0).
UseastandardtexteditingsoftwarelikeNotepadtomakechangestothe
modem.inifile.
Using ION Enterprise software:
IONEnterpriseusesdatabasequeriestoconfigurethelocalmodemsettings.
Databasequeriesarebeyondthescopeofthistechnicalnote.Ifyouwanttolearn
howtoconfigurethelocalmodemusingIONEnterprise,pleasecontactSchneider
ElectricTechnicalSupport.