sigmadue - IEC 61131-3 Function Block Library
154
5-3-25 MB_SLV_WR8_REAL
FB Prototype
MB_SLV_WR8_REAL
Input parameters
Output parameters
Description
This Function Block writes 8 REAL values passed with
DATA1 – DATA8
parame-
ters to the memory area starting from the passed register (
REGISTER
). The output
of the module (
OPRS
) is used to detect if the operation is performed correctly.
The setting
AD_MODE
allows the user to select if the
REGISTER
input base is 0
(
AD_MODE = FALSE
) or 1 (
AD_MODE
= TRUE). The default value for
AD_MODE
is TRUE.
Reference
tables
Here are reported the range of the parameters used by the function block.
Protocol
OPRS
Label Type Description
PROTOCOL ASCON_SERIALPROTOCOL Reference Protocol
REGISTER UINT Register
DATA1 – DATA8 REAL Data
AD_MODE BOOL
Addressing Mode Setting
(default value = TRUE)
Label Type Description
OPRS USINT Function block result
PROTOCOL
REGISTER
DATA1
DATA2
DATA3
DATA4
DATA5
DATA6
DATA7
DATA8
AD_MODE
ASCON_SERIALPROTOCOL
UINT
REAL
REAL
REAL
REAL
REAL
REAL
REAL
REAL
BOOL
USINT OPR
S
Protocol Description
SLAVE1 Protocol Modbus Slave 1
SLAVE2 Protocol Modbus Slave 2
OPRS Description
0 Service executed correctly
1 Address not allowed
3 Protocol number not valid